翻訳と辞書
Words near each other
・ Single-molecule magnetic sequencing
・ Single-nucleotide polymorphism
・ Single-O
・ Single-occupancy vehicle
・ Single-occupant vehicle
・ Single-origin coffee
・ Single-page application
・ Single-pair
・ Single-pair high-speed digital subscriber line
・ Single-parent homeschooling
・ Single-particle spectrum
・ Single-party period of the Republic of Turkey
・ Single-party state
・ Single-pass bore finishing
・ Single-payer health care
Single-phase electric power
・ Single-phase generator
・ Single-photon
・ Single-photon avalanche diode
・ Single-photon emission computed tomography
・ Single-photon source
・ Single-Pilot Resource Management
・ Single-player video game
・ Single-point locking
・ Single-point urban interchange
・ Single-port laparoscopy
・ Single-precision floating-point format
・ Single-price auction
・ Single-purpose
・ Single-reed instrument


Dictionary Lists
翻訳と辞書 辞書検索 [ 開発暫定版 ]
スポンサード リンク

Single-phase electric power : ウィキペディア英語版
Single-phase electric power

In electrical engineering, single-phase electric power is the distribution of alternating current electric power using a system in which all the voltages of the supply vary in unison. Single-phase distribution is used when loads are mostly lighting and heating, with few large electric motors. A single-phase supply connected to an alternating current electric motor does not produce a revolving magnetic field; single-phase motors need additional circuits for starting, and such motors are uncommon above 10 kW in rating.
In contrast, in a three-phase system, the currents in each conductor reach their peak instantaneous values sequentially, not simultaneously; in each cycle of the power frequency, first one, then the second, then the third current reaches its maximum value. The waveforms of the three supply conductors are offset from one another in time (delayed in phase) by one-third of their period. When the three phases are connected to windings around the interior of a motor stator, they produce a revolving magnetic field; such motors are self-starting.
Standard frequencies of single-phase power systems are either 50 or 60 Hz. Special single-phase traction power networks may operate at 16.67 Hz or other frequencies to power electric railways.
In some countries such as the United States, single phase is commonly divided in half to create split-phase electric power for household appliances and lighting.
==Splitting out==
No arrangement of transformers can convert a single-phase load into a balanced load on a polyphase system. A single-phase load may be powered from a three-phase distribution system either by connection between a phase and neutral or by connecting the load between two phases. The load device must be designed for the voltage in each case. The neutral point in a three phase system exists at the mathematical center of an equilateral triangle formed by the three phase points, and the phase-to-phase voltage is accordingly √3 times the phase-to-neutral voltage.〔See three phase. This arises from the phase difference between the conductors. If two conductors are energized with ac voltages that are the same magnitude and in-phase, there will be no voltage difference between them. If the voltages are the same magnitude and one voltage is delayed one-half cycle with respect to the other, the voltage between the two will be double. In a three phase system the phase difference between conductors is one-third of a cycle; a little bit of algebra would show that the voltage difference between two conductors is the square root of three times the magnitude of the phase to neutral voltage.〕 For example, in places using a 415 volt 3 phase system, the phase-to-neutral voltage is 240 volts, allowing single-phase lighting to be connected phase-to-neutral and three-phase motors to be connected to all three phases.
In North America, a typical three-phase system will have 208 volts between the phases and 120 volts between phase and neutral. If heating equipment designed for the 240-volt three-wire single phase system is connected to two phases of a 208 volt supply, it will only produce 75% of its rated heating effect. Single-phase motors may have taps to allow their use on either 208 V or 240 V supplies.
On higher voltage systems (on the order of kilovolts) where a single phase transformer is in use to supply a low voltage system, the method of splitting varies. In North American utility distribution practice, the primary of the step-down transformer is wired across a single high voltage feed wire and neutral, at least for smaller supplies (see photo of transformer on right). Rural distribution may be a single phase at a medium voltage; in some areas single wire earth return distribution is used when customers are very far apart. In Britain the step-down primary is wired phase-phase.